MK series boilers (heat exchangers)

MK series boilers are used for heating of large sized residential and industrial premises and supplying heat for technological needs.

MK series boilers are to be installed on or near combustion chamber. Enforced circulation pumps are mounted on the servicing door shielding.

Heat exchanger may be delivered with pneumatic cleaning system (optional).

Boilers may be delivered with heat insulation or corrugated steel shielding or it may be mounted in the heat plant.

Boiler model

K-720MK

K-1000MK

K-1500MK

K-2000MK

K-2500MK

K-3000MK

K-3500MK

K-4000MK

K-5000MK

Boiler type

Water heating boiler with mechanical burning chamber, smoke tubes

Nominal heating output (QN),  kW

720

1000

1500

2000

2500

3000

3500

4000

5000

Minimal heating output (Qmin),  kW

216

300

450

600

750

900

1050

1200

1500

Efficiency, %

85

85

85

85

85

85

85

85

85

Aerodynamic resistance at QN, not more than, Pa

600

630

655

680

700

720

740

760

800

Exhaust temperature at boiler flue outlet, °C

180

180

180

180

180

180

180

180

180

Exhaust volume, m3/h

2279

3166

4749

6363

7915

9499

11082

12665

15831

Smoke exhaust pipe dimensions, mm

1010×430

1010×430

1190×185

1510×252

1510×252

1510×252

1510×252

1510×252

1510×252

Operating water pressure, MPa (bar)

6 (0,6)

6 (0,6)

6 (0,6)

6 (0,6)

6 (0,6)

6 (0,6)

6 (0,6)

6 (0,6)

6 (0,6)

Minimum return water temperature during operation, ºC

60

60

60

60

60

60

60

60

60

Maximum permitted operating water temperature, ºC

110

110

110

110

110

110

110

110

110

Water flow, at Δt =20 ºC, t/h

30,78

42,76

64,15

85,54

106,93

128,32

149,71

171,1

213,88

Minimum water flow, t/h

20,64

28,66

42,99

57,32

71,65

85,98

100,31

114,64

143,3

Hydraulic resistance at Δt =20 ºC, mm H2O st

0…400

0…400

0…400

0…390

0…400

0…410

0…420

0…430

0…450

Water volume in the boiler, m³

2,8

2,9

5,2

10,6

10,8

11,1

11,3

11,6

12,4

Heat exchange area, m²

58,5

60

145

268

279

290

301

312

334

Connection pipes

conditional diameter, mm (inches)

65 (2½”)

65 (2½”)

133

133

133

133

133

133

133

flange diameter, Ø mm

160

160

241

241

241

241

241

241

241

Mass (not greater than), kg

4300

4500

7000

15000

15500

16000

16500

17000

18000

 

Boiler type

K-720MK

K-1000MK K-1500MK K-2000MK K-2500MK K-3000MK K-3500MK K-4000MK K-5000MK
H, mm

2390

2590 3150 4000 4010 4010 4010 4010 4010
B, mm 1560 1560 2130 2950 2960 2960 2960 2960 2960
L, mm 3780 3780 3610 4430 5110 5230 5390 5540 5860
B1, mm 1290 1290 1810 1840 2310 2310 2310 2310 2310
L1, mm 3100 3100 3100 3100 3880 4060 4220 4370 4700

Recommended connection to the heating system diagram: